H6: Pulse Train Input/Output - YASKAWA AC Drive-A1000 Technical Manual

High performance vector control drive
Table of Contents

Advertisement

B.9 H Parameters: Multi-Function Terminals
No.
(Addr.
Name
Hex)
H5-12
Run Command Method
(43D)
Selection
<1> If this parameter is set to 0, the drive will be unable to respond to MEMOBUS/Modbus commands.
u

H6: Pulse Train Input/Output

No.
(Addr.
Name
Hex)
H6-01
Pulse Train Input Terminal
(42C)
RP Function Selection
H6-02
(42D)
Pulse Train Input Scaling
H6-03
(42E)
Pulse Train Input Gain
H6-04
(42F)
Pulse Train Input Bias
H6-05
(430)
Pulse Train Input Filter Time
H6-06
Pulse Train Monitor
(431)
Selection
H6-07
(432)
Pulse Train Monitor Scaling
H6-08
Pulse Train Input Minimum
(43F)
Frequency
426
All Modes
0: FWD/Stop, REV/Stop
1: Run/Stop, FWD/REV
All Modes
0: Frequency reference
1: PID feedback value
2: PID setpoint value
3: V/f Control with Simple PG feedback (possible only when using motor 1
in V/f Control)
All Modes
Sets the terminal RP input signal frequency that is equal to 100% of the value
selected in H6-01.
All Modes
Sets the level of the value selected in H6-01 when a frequency with the value
set in H6-02 is input.
All Modes
Sets the level of the value selected in H6-01 when 0 Hz is input.
All Modes
Sets the pulse train input filter time constant.
All Modes
Select the pulse train monitor output function (value of the o-oo part of
Uo-oo).
For example, enter "501" for U5-01.
All Modes
Sets the terminal MP output signal frequency when the monitor value is 100%.
To have the pulse train monitor output equal the output frequency, set H6-06
to 2 and H6-07 to 0.
All Modes
Sets the minimum frequency for the pulse train input to be detected. Enabled
when H6-01 = 0, 1, or 2.
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual
Description
Description
Values
Page
Default: 0
470
Range: 0, 1
Values
Page
Default: 0
235
Range: 0 to 3
Default: 1440 Hz
Min.: 1000
236
Max.: 32000
Default: 100.0%
Min.: 0.0
237
Max.: 1000.0
Default: 0.0%
Min.: -100.0
237
Max.: 100.0
Default: 0.10 s
Min.: 0.00
237
Max.: 2.00
Default: 102
237
Range: 000 to 809
Default: 1440 Hz
Min.: 0
237
Max.: 32000
Default: 0.5 Hz
Min.: 0.1
237
Max.: 1000.0