5.7 H: Terminal Functions
The output closes when the motor is operating at the torque limit specified by the L7-oo parameters or an analog input. This
setting can only be used in OLV, CLV, AOLV/PM and CLV/PM control modes.
page 262
for details.
Setting 31: During Speed Limit
Note: PM motor control modes are not available on 600 V class drives, CIMR-Ao5oooooooo.
The output closes when the speed limit has been reached. This function can be used in CLV and CLV/PM control modes.
Status
Open
The conditions described below are not present.
1. The frequency reference has reached the upper limit set in d2-01.
2. The frequency reference has fallen to the lower limit set in d2-02 or d2-03.
Closed
3. Parameter b1-05 is set to 1, 2, or 3, and the frequency reference has fallen below the minimum output frequency
(E1-09).
Setting 32: During Speed Limit in Torque Control
The motor torque and load torque are not in balance, causing the motor to accelerate. The output closes when the motor reaches
the speed limit.
Refer to d5: Torque Control on page 178
details.
Setting 33: Zero Servo Complete
The output closes when Zero Servo is enabled and the load is locked into position within the allowable deviation (b9-02).
Refer to b9: Zero Servo on page 153
Setting 37: During Frequency Output
The output closes when the drive is outputting a frequency.
Status
Open
Drive is stopped or one of the following functions is being performed: baseblock, DC Injection Braking, Short Circuit Braking.
Closed
Drive is outputting frequency.
Setting 38: Drive Enable
Reflects the status of a digital input configured as a "Drive enable" input (H1-oo = 6A). If that digital input closes, then the
digital output set for "Drive enable" will also close.
Setting 39: Watt Hour Pulse Output
Outputs a pulse to indicate the watt hours.
Setting 3C: LOCAL/REMOTE Status
The output terminal closes while the drive is set for LOCAL and opens when in REMOTE.
Status
REMOTE: The external reference that has been selected (either b1-01 and b1-02 or b1-15 and b1-16) is used as frequency reference
Open
and Run command source
Closed
LOCAL: The digital operator is used as frequency reference and Run command source
226
for information on Zero Servo operation.
OFF
ON
run command
baseblock
OFF
command
output
frequency
OFF
ON
during run
OFF
during frequency
output
Figure 5.76 During Frequency Output Time Chart
Refer to H2-06: Watt Hour Output Unit Selection on page 227
Description
and
Indicating Operation at the Speed Limit
Description
ON
ON
Description
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual
Refer to L7-01 to L7-04: Torque Limits on
on page
180
for
for details.