U3: Fault History - YASKAWA AC Drive-A1000 Technical Manual

High performance vector control drive
Table of Contents

Advertisement

No.
(Addr.
Name
Hex)
U2-11
Input Terminal Status at
(8A)
Previous Fault
U2-12
Output Terminal Status at
(8B)
Previous Fault
U2-13
Drive Operation Status at
(8C)
Previous Fault
U2-14
Cumulative Operation
(8D)
Time at Previous Fault
Soft Starter Speed
U2-15
Reference at Previous
(7E0)
Fault
U2-16
Motor q-Axis Current at
(7E1)
Previous Fault
U2-17
Motor d-Axis Current at
(7E2)
Previous Fault
U2-19
Rotor Deviation at
(7EC)
Previous Fault
U2-20
Heatsink Temperature at
(8E)
Previous Fault
<1> The number of decimal places in the parameter value depends on the drive model and the ND/HD selection in parameter C6-01. This value has two
decimal places (0.01 A) if the drive is set for a maximum applicable motor capacity up to and including 11 kW, and one decimal place (0.1 A) if
the maximum applicable motor capacity is higher than 11 kW.
<2> When reading the value of this monitor via MEMOBUS/Modbus, a value of 8192 is equal to 100% of the drive rated output current.
u

U3: Fault History

No.
(Addr.
Name
Hex)
U3-01 to
U3-04
First to 4th Most Recent
(90 to 93
Fault
(800 to
803))
U3-05 to
U3-10
5th to 10th Most Recent
(804 to
Fault
809)
U3-11 to
U3-14
Cumulative Operation
(94 to 97
Time at 1st to 4th Most
(80A to
Recent Fault
80D))
U3-15 to
Cumulative Operation
U3-20
Time at 5th to 10th Most
(80E to
Recent Fault
813)
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual
Description
All Modes
Displays the input terminal status at the previous fault. Displayed as in
U1-10.
All Modes
Displays the output status at the previous fault. Displays the same status
displayed in U1-11.
All Modes
Displays the operation status of the drive at the previous fault. Displays the
same status displayed in U1-12.
All Modes
Displays the cumulative operation time at the previous fault.
All Modes
Displays the speed reference for the soft starter at the previous fault.
V/f
V/f
V/f w PG
V/f w PG
OLV
OLV
OLV
OLV
OLV/PM
OLV/PM
OLV/PM
OLV/PM
AOLV/PM
AOLV/PM
AOLV/PM
AOLV/PM
CLV/PM
CLV/PM
CLV/PM
CLV/PM
Displays the q-axis current for the motor at the previous fault.
V/f
V/f
V/f w PG
V/f w PG
OLV
OLV
OLV
OLV
OLV/PM
OLV/PM
OLV/PM
OLV/PM
AOLV/PM
AOLV/PM
AOLV/PM
AOLV/PM
CLV/PM
CLV/PM
CLV/PM
CLV/PM
Displays the d-axis current for the motor at the previous fault.
V/f
V/f
V/f w PG
V/f w PG
OLV
OLV
OLV/PM
OLV/PM
AOLV/PM
AOLV/PM
AOLV/PM
AOLV/PM
CLV/PM
CLV/PM
Displays the degree of rotor deviation when the most recent fault occurred
(same status will appear as shown in U6-10).
All Modes
Displays the temperature of the heatsink when the most recent fault
occurred.
Description
All Modes
Displays the first to the fourth most recent faults.
All Modes
Displays the fifth to the tenth most recent faults.
All Modes
Displays the cumulative operation time when the first to the fourth most
recent faults occurred.
All Modes
Displays the cumulative operation time when the fifth to the tenth most
recent faults occurred.
CLV
CLV
CLV
CLV
CLV
CLV
CLV
CLV
CLV
CLV
B.15 U: Monitors
Analog Output
Unit
Level
No signal output
available
No signal output
available
No signal output
available
No signal output
1 h
available
No signal output
0.01 Hz
available
No signal output
0.10%
available
No signal output
0.10%
available
No signal output
0.1 deg
available
No signal output
1 °C
available
Analog Output
Unit
Level
No signal output
available
No signal output
available
No signal output
1 h
available
No signal output
1 h
available
451
B

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents