5.6 F: Option Settings
n
F6-01: Communications Error Operation Selection
Determines drive operation when a communication error occurs.
No.
F6-01
Setting 0: Ramp to stop (uses the deceleration time set to C1-02)
Setting 1: Coast to stop
Setting 2: Fast Stop (uses the Fast Stop time set to C1-09)
Setting 3: Alarm only (continue operation)
n
F6-02: External Fault from Comm. Option Detection Selection
Determines the detection method of an external fault initiated by a communication option (EF0).
No.
F6-02
External Fault from Comm. Option Detection Selection
Setting 0: Always detected
Setting 1: Detection during run only
n
F6-03: External Fault from Comm. Option Operation Selection
Determines drive operation when an external fault is initiated by a communication option (EF0).
No.
F6-03
External Fault from Comm. Option Operation Selection
Setting 0: Ramp to stop
Setting 1: Coast to stop
Setting 2: Fast Stop
Setting 3: Alarm only (continue operation)
n
F6-06: Torque Reference/Torque Limit Selection from Comm. Option
Selects whether torque reference and torque limit values are assigned to the drive from the network.
No.
F6-06
Torque Reference/Torque Limit Selection from Comm. Option
Setting 0: Enabled
Setting 1: Disabled
n
F6-07: NetRef/ComRef Function Selection
Selects the treatment of multi-step speed inputs when the NetRef command is set.
No.
F6-07
Setting 0: Multi-step speed operation disabled
Multi-step speed input frequency references are disabled when the NetRef command is selected.
Setting 1: Multi-step speed operation enabled
Multi-step speed inputs are still active and can override the frequency reference from the communications option even when
the NetRef command is selected.
202
Parameter Name
Communications Error Operation Selection
Parameter Name
Parameter Name
Parameter Name
Parameter Name
NetRef/ComRef Function Selection
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual
Setting Range
0 to 3
Setting Range
0, 1
Setting Range
0 to 3
Setting Range
0, 1
Setting Range
0, 1
Default
1
Default
0
Default
1
Default
0
Default
0