Setting 12: Timer Output
This setting configures a digital output terminal as the output for the timer function.
for details.
Setting 13: Speed Agree 2 (f
The output closes when the actual output frequency or motor speed (CLV, CLV/PM) is within the speed agree width (L4-04)
of the current frequency reference, regardless of the direction.
Status
Open
Output frequency or motor speed does not match the frequency reference while the drive is running.
Closed
Output frequency or motor speed is within the range of frequency reference ±L4-04.
Note: Detection works in forward and reverse.
Output Frequency
Speed Agree 2
Refer to L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-) on page 256
Setting 14: User-Set Speed Agree 2 (f
The output closes when the actual output frequency or motor speed (CLV, CLV/PM) and the frequency reference are within
the speed agree width (L4-04) of the programmed speed agree level (L4-03).
Status
Open
Output frequency or motor speed and frequency reference are both outside the range of L4-03 ±L4-04
Closed
Output frequency or motor speed and the frequency reference are both with in the range of L4-03 ±L4-04
Note: The detection level L4-03 is a signed value; detection works in the specified direction only.
Frequency
reference
Speed Agree 2
Refer to L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-) on page 256
Setting 15: Frequency Detection 3
The output opens when the output frequency or motor speed (CLV, CLV/PM) rises above the detection level set in L4-03 plus
the detection with set in L4-04. The terminal remains open until the output frequency or motor speed falls below the level set
in L4-03. The detection level L4-03 is a signed value; detection works in the specified direction only.
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual
/f
Agree 2)
ref
out
Frequency
reference
or Motor Speed
OFF
ON
Figure 5.71 Speed Agree 2 Time Chart
/f
Agree 2)
ref
set
Output Frequency
or Motor Speed
User Set
OFF
ON
Figure 5.72 User-Set Speed Agree 2 Example with a Positive L3-04 Value
Refer to b4: Delay Timers on page 140
Description
L4-04
Description
L4-03
Output Frequency
+/- L4-04
or Motor Speed
Frequency
reference
5.7 H: Terminal Functions
L4-04
for more details.
for more details.
5
223