F1-34
PG 2 Gear Teeth 2
(3B3)
F1-35
PG 2 Division Rate for Pulse
(3BE)
Monitor
F1-36
PG Option Card Disconnect
(3B5)
Detection 2
F1-37
PG 2 Signal Selection
(3BD)
<1> Default setting is determined by parameter A1-02, Control Mode Setting.
u

F2: Analog Input Card (AI-A3)

No.
(Addr.
Name
Hex)
F2-01
Analog Input Option Card
(38F)
Operation Selection
F2-02
Analog Input Option Card
(368)
Gain
F2-03
Analog Input Option Card
(369)
Bias
u

F3: Digital Input Card (DI-A3)

No.
(Addr.
Name
Hex)
F3-01
Digital Input Option Card
(390)
Input Selection
F3-03
Digital Input Option DI-A3
(3B9)
Data Length Selection
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual
Description
V/f
V/f w PG
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
Sets the gear ratio between the motor shaft and the encoder (PG). A gear ratio
of 1 will be used if F1-33 or F1-34 are set to 0.
V/f
V/f
V/f w PG
V/f w PG
V/f w PG
V/f w PG
OLV
OLV
OLV/PM
OLV/PM
AOLV/PM
AOLV/PM
CLV/PM
CLV/PM
Sets the division ratio for the pulse monitor used of the PG option card 2
installed to port CN5-B.
By setting "xyz", the division ratio becomes = [(1 + x) / yz].
V/f
V/f
V/f w PG
V/f w PG
V/f w PG
V/f w PG
OLV
OLV
OLV/PM
OLV/PM
AOLV/PM
AOLV/PM
CLV/PM
CLV/PM
0: Disabled
1: Enabled
V/f
V/f w PG
V/f w PG
OLV
OLV/PM
AOLV/PM
CLV/PM
0: A pulse detection
1: AB pulse detection
Description
All Modes
0: Option card input terminals V1, V2, and V3 replace drive input terminals
A1, A2, and A3.
1: Input signals to terminals V1, V2, and V3 are added together to create the
frequency reference.
All Modes
Sets the gain for the input signal to the analog card.
All Modes
Sets the bias for the input signal to the analog card.
Description
All Modes
0: BCD, 1% units
1: BCD, 0.1% units
2: BCD, 0.01% units
3: BCD, 1 Hz units
4: BCD, 0.1 Hz units
5: BCD, 0.01 Hz units
6: BCD customized setting (5 digit), 0.02 Hz units
7: Binary input
When the digital operator units are set to be displayed in Hertz or user-set units
(o1-03 = 2 or 3), the units for F3-01 are determined by parameter o1-03.
All Modes
0: 8 bit
1: 12 bit
2: 16 bit
CLV
CLV
CLV
CLV
CLV
CLV
CLV
CLV
CLV
CLV
B.8 F: Options
Values
Page
Default: 0
Min.: 0
197
Max.: 1000
Default: 1
Min.: 1
197
Max.: 132
Default: 1
198
Range: 0, 1
Default: 0
198
Range: 0, 1
Values
Page
Default: 0
199
Range: 0, 1
Default: 100.0%
Min.: -999.9
199
Max.: 999.9
Default: 0.0%
Min.: -999.9
199
Max.: 999.9
Values
Page
Default: 0
199
Range: 0 to 7
Default: 2
200
Range: 0 to 2
409