YASKAWA AC Drive-A1000 Technical Manual page 267

High performance vector control drive
Table of Contents

Advertisement

Setting 3: Finless drive or external heatsink Installation
For finless drives or a standard drive mounted with the heatsink outside the cabinet or enclosure panel.
n
L8-38: Carrier Frequency Reduction Selection
Selects the operation of the carrier frequency reduction function. Reduces the carrier frequency when the output current exceeds
a certain level. This temporarily increases the overload capability (oL2 detection), allowing the drive to run through transient
load peaks without tripping.
Note: This function cannot be used in AOLV/PM.
No.
L8-38
Setting 0: Disabled
No carrier frequency reduction at high current.
Setting 1: Enabled for output frequencies below 6 Hz
The carrier frequency is reduced at speeds below 6 Hz when the current exceeds 100% of the drive rated current. The drive
returns to the normal carrier frequency when the current falls below 88% or the output frequency exceeds 7 Hz.
Setting 2: Enabled for entire frequency range
The carrier frequency is reduced at the following speeds:
• Below 6 Hz when the current exceeds 100% of the drive rated current.
• Above 7 Hz when the current exceeds 112% of the drive rated current.
The drive uses the delay time set in parameter L8-40 and a hysteresis of 12% when switching the carrier frequency back to
the set value.
n
L8-40: Carrier Frequency Reduction Off-Delay Time
Sets a hold time before returning to the original carrier frequency setting after the carrier frequency has been temporarily
derated as determined by L8-38. The carrier frequency reduction function is disabled when this value is 0.00 s.
No.
L8-40
Carrier Frequency Reduction Off-Delay Time
n
L8-41: High Current Alarm Selection
Triggers a high current alarm (HCA) when the output current rises exceeds 150% of the drive rated current.
No.
L8-41
Setting 0: Disabled
No alarm is detected.
Setting 1: Enabled
An alarm is triggered when the output current exceeds 150% of the drive rated current. A digital output set for an alarm (H2-
oo = 10) will close.
n
L8-55: Internal Braking Transistor Protection
Enables or disables protection for the internal braking transistor.
No.
L8-55
Setting 0: Disabled
Disable braking transistor protection when not using the internal braking transistor, including the following instances:
• When using a regen converter such as DC5.
• When using a regen unit such as RC5.
• When using external braking transistor options like CDBR units.
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual
Name
Carrier Frequency Reduction Selection
Name
Name
High Current Alarm Selection
Name
Internal Braking Transistor Protection
5.8 L: Protection Functions
Setting Range
Determined by
0 to 2
A1-02, C6-01 and
Setting Range
Determined by
0.00 to 2.00 s
Setting Range
0, 1
Setting Range
0, 1
Default
o2-04
Default
A1-02
Default
0
5
Default
0
267