F4: Analog Monitor Card Settings - YASKAWA AC Drive-A1000 Technical Manual

High performance vector control drive
Table of Contents

Advertisement

5.6 F: Option Settings
Setting 2: BCD, 0.01% units
Setting 3: BCD, 1 Hz units
Setting 4: BCD, 0.1 Hz units
Setting 5: BCD, 0.01 Hz units
Setting 6: BCD, special setting (5 digit input), 0.02 Hz units
Setting 7: Binary
n
F3-03: Digital Input Option DI-A3 Data Length Selection
Determines the number of bits for the option card input that sets the frequency reference.
No.
F3-03
Digital Input Option DI-A3 Data Length Selection
Setting 0: 8 bit
Setting 1: 12 bit
Setting 2: 16 bit
u

F4: Analog Monitor Card Settings

These parameters set the drive for operation with the analog output option card AO-A3. Refer to the instruction manual
packaged with the option card for specific details on installation, wiring, input signal level selection, and parameter setup.
n
F4-01, F4-03: Terminal V1, V2 Monitor Selection
Selects the data to output from analog terminal V1. Enter the final three digits of Uo-ooto determine which monitor data
is output from the option card. Some monitors are only available in certain control modes.
No.
F4-01
F4-03
n
F4-02, F4-04, F4-05, F4-06: Terminal V1, V2 Monitor Gain and Bias
Parameters F4-02 and F4-04 determine the gain, while parameters F4-05 and F4-06 set the bias. These parameters are set as
a percentage of the output signal from V1 and V2 where 100% equals 10 V output. The terminal output voltage is limited to
10 V.
No.
F4-02
F4-04
F4-05
F4-06
Using Gain and Bias to Adjust Output Signal Level
When viewing the values set to F4-02 or F4-05 on the digital operator, a voltage equal to 100% of the parameter being viewed
(including current gain and bias settings) will be output from terminal V1 or V2. When viewing the value set to F4-05 or
F4-06, terminal V1 or V2 will output a voltage equal to 0% of the parameter being viewed (including current gain and bias
settings).
Example 1: F4-02 = 0%, F4-02 = 80%. When the parameter setting display for F4-02 is accessed using the digital operator,
terminal V1 will output a voltage of 8 V, even when the drive is stopped.
Example 2: F4-03 = 5%. When the parameter setting display for F4-03 is accessed using the digital operator, terminal V1 will
output a voltage of 0.5 V, even when the drive is stopped.
200
Parameter Name
Parameter Name
Terminal V1 Monitor Selection
Terminal V2 Monitor Selection
Parameter Name
Terminal V1 Monitor Gain
Terminal V2 Monitor Gain
Terminal V1 Monitor Bias
Terminal V2 Monitor Bias
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual
Setting Range
0 to 2
Setting Range
000 to 999
000 to 999
Setting Range
-999.9 to 999.9%
-999.9 to 999.9%
-999.9 to 999.9%
-999.9 to 999.9%
Default
2
Default
102
103
Default
100.0%
50.0%
0.0%
0.0%