Setting 0: During Run
Output closes when the drive is outputting a voltage.
Status
Open
Drive is stopped.
Closed
A Run command is input or the drive is in deceleration or DC injection.
Setting 1: Zero Speed
Terminal closes when the output frequency or motor speed (CLV, CLV/PM) falls below the minimum output frequency set
to E1-09 or b2-01.
Status
Open
Output frequency is above the minimum output frequency set to E1-09 or b2-01
Closed
Output frequency is less than the minimum output frequency set to E1-09 or b2-01
Note: In CLV and CLV/PM control modes, the zero speed level is defined by b2-01. In all other control modes, the zero speed level is the minimum
output frequency set to E1-09.
Output frequency
Setting 2: Speed Agree 1 (f
Closes when the actual output frequency or motor speed (CLV, CLV/PM) is within the Speed Agree Width (L4-02) of the
current frequency reference regardless of the direction.
Status
Open
Output frequency or motor speed does not match the frequency reference while the drive is running.
Closed
Output frequency or motor speed is within the range of frequency reference ±L4-02.
Note: Detection works in forward and reverse.
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual
OFF
ON
Run command
Baseblock
OFF
command
Output
frequency
OFF
ON
During Run
Figure 5.65 During Run Time Chart
or
motor speed
OFF
Zero Speed
Figure 5.66 Zero-Speed Time Chart
/f
Agree 1)
ref
out
Description
ON
Description
E1-09 (Max. Output Frequency) or
b2-01 (Zero Speed Level)
ON
Description
5.7 H: Terminal Functions