L7: Torque Limit

OLV/PM
OLV/PM
AOLV/PM
AOLV/PM
CLV/PM
CLV/PM
No.
(Addr.
Name
Hex)
L7-01
Forward Torque Limit
(4A7)
L7-02
Reverse Torque Limit
(4A8)
L7-03
Forward Regenerative
(4A9)
Torque Limit
L7-04
Reverse Regenerative
(4AA)
Torque Limit
L7-06
Torque Limit Integral Time
(4AC)
Constant
Torque Limit Control
L7-07
Method Selection during
(4C9)
Accel/Decel
u

L8: Drive Protection

OLV/PM
OLV/PM
AOLV/PM
AOLV/PM
CLV/PM
CLV/PM
No.
(Addr.
Name
Hex)
Internal Dynamic Braking
L8-01
Resistor Protection
(4AD)
Selection (ERF type)
L8-02
Overheat Alarm Level
(4AE)
L8-03
Overheat Pre-Alarm
(4AF)
Operation Selection
L8-05
Input Phase Loss Protection
(4B1)
Selection
L8-07
Output Phase Loss
(4B3)
Protection Selection
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual
PM motor control modes are not available on 600 V class drives, CIMR-Ao5oooooooo.
V/f
V/f
V/f w PG
V/f w PG
OLV/PM
OLV/PM
OLV/PM
OLV/PM
AOLV/PM
AOLV/PM
AOLV/PM
AOLV/PM
CLV/PM
CLV/PM
CLV/PM
CLV/PM
Sets the torque limit value as a percentage of the motor rated torque. Four
individual quadrants can be set.
L7-04
Regeneration
REV
L7-02
V/f
V/f w PG
OLV/PM
AOLV/PM
CLV/PM
Sets the integral time constant for the torque limit.
V/f
V/f w PG
OLV/PM
AOLV/PM
CLV/PM
0: Proportional control (changes to integral control at constant speed). Use this
setting when acceleration to the desired speed should take precedence over the
torque limit.
1: Integral control. Set L7-07 to 1 if the torque limit should take precedence.
PM motor control modes are not available on 600 V class drives, CIMR-Ao5oooooooo.
All Modes
0: Resistor overheat protection disabled
1: Resistor overheat protection enabled
All Modes
An overheat alarm will occur if the heatsink temperature exceeds the level set
in L8-02.
All Modes
0: Ramp to stop. A fault is triggered.
1: Coast to stop. A fault is triggered.
2: Fast Stop. Decelerate to stop using the deceleration time in C1-09. A fault
is triggered.
3: Continue operation. An alarm is triggered.
4: Continue operation at reduced speed as set in L8-19.
All Modes
Selects the detection of input current phase loss, power supply voltage
imbalance, or main circuit electrolytic capacitor deterioration.
0: Disabled
1: Enabled
All Modes
0: Disabled
1: Enabled (triggered by a single phase loss)
2: Enabled (triggered when two phases are lost)
Description
OLV
OLV
OLV
OLV
CLV
CLV
CLV
CLV
Output Torque
Positive Torque
L7-01
Motor
r/min
FWD
Regeneration
L7-03
Negative Torque
OLV
OLV
CLV
OLV
OLV
CLV
Description
B.10 L: Protection Function
Values
Page
Default: 200%
Min.: 0
Max.: 300
Default: 200%
Min.: 0
Max.: 300
Default: 200%
Min.: 0
Max.: 300
Default: 200%
Min.: 0
Max.: 300
Default: 200 ms
Min: 5
Max: 10000
Default: 0
Range: 0, 1
Values
Page
Default: 0
Range: 0, 1
<1>
Default:
Min.: 50 °C
Max.: 130 °C
Default: 3
Range: 0 to 4
Default: 1
Range: 0, 1
Default: 1
Range: 0 to 2
262
262
262
262
262
262
263
263
263
264
B
264
433