5.7 H: Terminal Functions
Terminal Status
Setting
N.O.
22
O
23
24
O
25
26
O
27
28
O
29
2A
O
2B
2C
O
2D
2E
O
2F
<1> Determine the terminal status for each fault, i.e., whether the terminal is normally open or normally closed.
<2> Determine whether detection for each fault should be enabled only during run or always detected.
Setting 30: PID Integral Reset
Configuring one of the digital inputs for PID integral reset (H1-oo = 30) resets the value of the integral component in PID
control to 0 when the terminal is closed.
Setting 31: PID Integral Hold
Configuring a digital input for Integral Hold (H1-0o = 31) locks the value of the integral component of the PID control as
long as the input is active. The PID controller resumes integral operation from the hold value as soon as the integral hold input
is released.
Refer to PID Block Diagram on page 143
Setting 32: Multi-Step Speed Reference 4
Selects the multi-step speeds d1-09 to d1-16 in combination with the input terminal set for Multi-Step Speed 1, 2 and 3.
to d1-01 to d1-17: Frequency Reference 1 to 16 and Jog Frequency Reference on page
Setting 34: PID Soft Starter Cancel
A digital input configured as a PID soft starter cancel input (H1-0o = 34) enables or disables the PID soft starter and cancels
the PID accel/decel time (b5-17).
Setting 35: PID Input Level Selection
Allows an input terminal to switch the sign of the PID input.
Setting 40, 41: Forward Run, Reverse Run Command for 2-Wire Sequence
Configures the drive for a 2-Wire sequence.
When an input terminal set to 40 closes, the drive operates in the forward direction. When an input set for 41 closes, the drive
operates in reverse. Closing both inputs simultaneously will result in an external fault.
Note: 1. This function cannot be used simultaneously with settings 42 and 43.
2. The same functions are assigned to terminals S1 and S2 when the drive is initialized for 2-Wire sequence.
214
<1>
Detection Conditions
Always
N.C.
during Run
Detected
O
O
O
O
O
O
O
O
O
O
O
O
O
Refer to PID Block Diagram on page 143
Refer to PID Block Diagram on page
Forward Run
Reverse Run
Figure 5.63 Example Wiring Diagram for 2-Wire Sequence
<2>
Detected
Ramp to Stop
(fault)
only
O
O
O
O
O
O
O
O
O
O
for more information on this function.
143.
Refer to PID Block Diagram on page 143
Drive
S1
S2
SC
Digital Input Common
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual
Stopping Method
Coast to Stop
Fast Stop
(fault)
(fault)
O
O
O
O
O
O
O
O
for more details.
169.
Alarm Only
(continue
running)
O
O
O
O
Refer
for details.