Alm (Servo Alarm) Signal - YASKAWA SGD7S-****20A Series Product Manual

Servopack with mechatrolink-iii communications references, ac servo drive
Table of Contents

Advertisement

6.1 I/O Signal Allocations

6.1.3 ALM (Servo Alarm) Signal

Forcing Outputs with MECHATROLINK-III Commands
You can use the servo command I/O signal (SVCMD_IO) command through MECHATROLINK-
III communications to force outputs on general-purpose sequence output 1 (SO1) to general-
purpose sequence output 3 (SO3).
Use Pn56A = n.XXX to set the output signal reference method for SO1 to SO3.
Refer to the following manual for detailed information on the servo command I/O signal (SVCM-
D_IO) command.
Σ-7-Series MECHATROLINK-III Communications Standard Servo Profile Command Manual (Manual No.: SIEP
S800001 31)
Pn56A
Example
Important
6.1.3

ALM (Servo Alarm) Signal

This signal is output when the SERVOPACK detects an error.
Important
Type
Output
Alarm Reset Methods
Refer to the following section for information on the alarm reset methods.
12.2.3 Resetting Alarms on page 12-43
6-8
Parameter

n.
0
(default set-
Output parameter-assigned SO1 signal.
ting)
Output OR of parameter-assigned SO1 signal

n.
1
and signal set by SVCMD_IO.

n.
0
(default set-
Output parameter-assigned SO2 signal.
ting)
Output OR of parameter-assigned SO2 signal

n.
1
and signal set by SVCMD_IO.

n.
0
(default set-
Output parameter-assigned SO3 signal.
ting)
Output OR of parameter-assigned SO3 signal

n.
1
and signal set by SVCMD_IO.
If you change the setting of Pn56A from the default setting to n.1, an OR of the /BK
signal and the signal that is set with the servo command I/O signal (SVCMD_IO) command
will be output.
To output only the signal that is set with the servo command I/O signal (SVCMD_IO) command on
SO1 to SO3, disable the signal that is allocated with the parameter (i.e., set it to not use the sig-
nal).
Configure an external circuit so that this alarm output turns OFF the main circuit power supply to
the SERVOPACK whenever an error occurs.
Signal
Connector Pin No.
ALM
CN1-3 and CN1-4
Description
Signal Status
ON (closed)
Normal SERVOPACK status
OFF (open)
SERVOPACK alarm
When Enabled
Classification
After restart
Setup
Meaning