Advertisement

5-14 Other Functions

The following explains the functions other than those relating to operation settings, such as
initialization setting functions.

Initialization Setting

The set values can be initialized to the factory defaults. The fault monitor data can also be
cleared.
To prevent inadvertent initialization, initialization cannot be performed unless multiple
parameters are set.
Total RUN Time (d016) and Power ON Time Monitor (d017) cannot be cleared.
If Display Selection (b037) or Soft Lock Selection (b031) is set, initialization cannot be
performed because the following parameters used in initialization cannot be accessed. Cancel
the fixed display or soft lock and then perform initialization.
If you forget the password, there is no other means for recovery. Exercise due caution when
setting a password.
Parameter
No.
b084
b094
b085
b180
*1.Refer to the next page for the details of "input/output terminal/basic communication settings" when
Initialization Target Selection is set (b094 = 01).
*2.Only the data of user-registered parameters are initialized and the user-registered parameters themselves
remain.
*3.Exercise caution because when "01" is selected for Perform Initialization/Mode Selection (b180) and
the Enter key is pressed, initialization starts immediately and the process cannot be undone.
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
Function name
00: Initialization disabled
01: Fault monitor clear
Initialization
02: Initializes data
Selection
03: Fault monitor clear + Data initialization
04: Do not set.
00: All data (Complete initialization)
01: Initialize all data other than input/output
terminal/basic communication
settings
Initialization
02: Initialize only user-set/registered
Target Selection
functions (U001 to U032)
03: Initialize all data other than user-set/
registered functions (U001 to U032) and
Display Selection (b037)
Initialization Data
00: Do not change.
Selection
00: Initialization disabled
Perform
Initialization/Mode
01: Perform initialization/mode selection
*3
Selection

5-14 Other Functions

Data
*1
*2
Default
Unit
setting
00
00
00
00
5-174
5