4.9.2

Sinusoidal filter (option L15)

Description
The sinusoidal filter limits the voltage gradient and the capacitive charge/discharge currents
which usually occur with inverter operation. It also prevents additional noise caused by the
pulse frequency. The service life of the motor is as long as that attained with direct mains
operation.
CAUTION
If a sinusoidal filter is connected to the converter, the converter must be activated during
commissioning to prevent the filter from being destroyed (see "Commissioning").
Constraints
The following constraints should be noted when a sinusoidal filter is used:
● The output frequency is limited to no more than 150 Hz.
● The modulation type is permanently set to space-vector modulation without
● Maximum permissible motor cable lengths:
● During commissioning, the pulse frequency rises to double the factory setting. This
Table 4-19
The values apply to operation with a sinusoidal filter and do not correspond with the rated
1)
current on the type plate.
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A
overmodulation. This reduces the maximum output voltage to approx. 85% of the rated
output voltage.
– Unshielded cable: max. 150 m
– Shielded cable: max. 100 m
induces current derating, which must be applied to the cabinet unit rated currents listed in
the technical specifications.
Note
If a filter cannot be parameterized (p0230 ≠ 3), this means that a filter has not been
provided for the cabinet unit. In this case, the cabinet unit must not be operated with a
sinusoidal filter.
Technical specifications for sinusoidal filters with SINAMICS S150
Order no.
SINAMICS S150
6SL3710-1LE32-1AA0
6SL3710-1LE32-6AA0
6SL3710-1LE33-1AA0
6SL3710-1LE33-8AA0
6SL3710-1LE35-0AA0
Voltage
Pulse frequency
[V]
380 – 480 V 3 AC
380 – 480 V 3 AC
380 – 480 V 3 AC
380 – 480 V 3 AC
380 – 480 V 3 AC
Electrical installation
4.9 Other connections
Output current
[kHz]
[A]
4
172 A
4
216 A
4
273 A
4
331 A
4
382 A