4.9.23

Electrically separate 24 V DC power supply for NAMUR (option B02)

Description
If the customer cannot provide a separate 24 V DC supply (PELV), this option enables a
second power supply to be installed to provide the PELV (terminal assignment as option
B00, 24 V infeed at terminal –A1-X1:1,2,3 no longer needed).
4.9.24

Outgoing section for external auxiliary equipment for NAMUR (option B03)

Description
If power is to be supplied to a motor fan on site, option B03 provides an uncontrolled fuse-
protected (10 A) outgoing section. As soon as the supply voltage is present at the converter
input, it is also present at these terminals. The voltage is the same as the converter input
voltage. You must take this into account when configuring the separately driven fan.
Connection
Table 4-53
Max. connectable cross-section: 2.5 mm² (AWG 12)
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A
Terminal block -A1-X1 – uncontrolled outgoing power unit (10 A) for supplying a
separately driven motor fan
Terminal
1, 2, 3, PE
Outgoing section for separately driven motor
Default value
fan
Electrical installation
4.9 Other connections
Comments