Electrical installation
4.9 Other connections
4.9.7

Cabinet anti-condensation heating (option L55)

Description
The anti-condensation heating is used at low ambient temperatures and high levels of
humidity to prevent condensation forming.
One 100 W heater is installed for a 400 mm and 600 mm cabinet panel, and two 100 W
heaters for an 800/1000 and 1200 mm cabinet panel. The power supply for the heating (110
V – 230 V AC) must be provided externally and fused at max. 16 A.
When the supply voltage for the cabinet anti-condensation heating is connected, dangerous
voltages are present in the cabinet unit even when the main circuit breaker is open.
Connection
Table 4-25
Terminal
Max. connectable cross-section: 4 mm
76
DANGER
Terminal block X240 – connection for cabinet anti-condensation heating
Designation
1
L1
2
N
3
PE
Technical specifications
110 V – 230 V AC
Voltage supply
Protective conductor
(AWG 10)
2
Operating Instructions, 07/07, A5E00288214A
Drive converter cabinet units