Siemens SINAMICS S150 Operating Instructions Manual page 64

Converter cabinet units 75 kw to 1200 kw
Hide thumbs Also See for SINAMICS S150:
Table of Contents

Advertisement

Electrical installation
4.8 Signal connections
X530: 4 digital inputs
Table 4-11
Terminal block X530
Terminal
1
2
3
4
5
6
DI: digital input; M2: ground reference; M: Electronics ground
1)
Max. connectable cross-section: 1.5 mm² (AWG 14)
Note
An open input is interpreted as "low".
To enable the digital inputs to work, terminal M2 must be connected. The following options
are available:
1. The provided ground reference of the digital inputs, or
2. a jumper to terminal M (notice: this removes isolation for these digital inputs).
X521: 2 analog inputs (differential inputs)
Table 4-12
Terminal block X521
Terminal
1
2
3
4
5
6
7
8
AI: analog input; P10/N10: auxiliary voltage, M: Ground reference
1)
Max. connectable cross-section: 1,5 mm² (AWG 14)
CAUTION
The input current of the analog inputs must not exceed 35 mA when current measurements
are performed.
64
Designation
1)
DI 4
Voltage: - 3 V to 30 V
Current input (typical): 10 mA up to 24 V
DI 5
With electrical isolation: The reference potential is terminal M2
DI 6
Level:
DI 7
- High signal level: 15 V to 30 V
M2
- Low signal level: -3 V to 5 V
M
Designation
1)
AI 0+
AI 0-
AI 1+
AI 1-
P10
M
N10
M
Technical specifications
Technical specifications
-10 V - +10 V, Ri = 70 kΩ
+4 mA - +20 mA
-20 mA - +20 mA, Ri = 250 Ω
0 mA - +20 mA (factory setting)
+10 V ± 1 %, Imax 5 mA
Reference potential for AI 0
-10 V ± 1 %, Imax 5 mA
Reference potential for AI 1
Operating Instructions, 07/07, A5E00288214A