Technical specifications
12.3 Technical specifications
Table 12-10 Version A, 380 V – 480 V 3 AC, part 2
Category
Order No. 6SL3710-
Rated motor output
at 400 V, 50 Hz
at 460 V, 60 Hz
Rated input voltage
Rated input current
1)
Rated output current
Base-load current I
2)
L
Base-load current I
H 3)
Max. output frequency
4)
Power loss
Cooling air requirement
Sound pressure level at 50/60 Hz
Line connection
Recommended: DIN VDE
Maximum: DIN VDE
AWG/MCM
Fixing screw
Motor connection
Recommended: DIN VDE
Maximum: DIN VDE
AWG/MCM
Fixing screw
Protective conductor connection
Fixing screw
Approx. weight (standard version)
Frame sizes
Active Interface Module
Active Line Module
Motor Module
Dimensions (standard version)
Width x height x depth
Recommended protection
Line protection
(with option L26)
Rated current
Frame size to DIN 43620-1
Line and semi-cond. protection
(without option L26)
Rated current
Frame size to DIN 43620-1
The currents are based on a power factor of cos ϕ = 1 and include 10 A for the external auxiliary equipment (as used, for
1)
example, with options L19 or B03).
The base-load current (I
2)
(see "Overload capability").
The base-load current (I
3)
(see "Overload capability").
Maximum output frequency at factory-set default pulse frequency (for information on increasing the output frequency,
4)
see "Functions, monitoring and protective functions/Increasing the output frequency"; for information on derating data, see
"Derating data").
The recommendations for the North American market in AWG or MCM must be taken from the appropriate NEC
5)
(National Electrical Code) or CEC (Canadian Electrical Code) standards.
484
Unit
7LE33-8AA0
kW
200
hp
300
V
A
349
A
380
A
370
A
340
Hz
160
kW
9.3
m³/s
1.19
dB(A)
72/74
mm
2 x 120
5)
2
mm
4 x 240
2
4 x (500)
M12 (2 holes)
mm
2 x 120
5)
2
mm
2 x 150
2
2 x (300)
M12 (2 holes)
M12 (2 holes)
kg
980
GI
GX
GX
mm
1800 x 2,000 x 600
3NA3365
A
500
3
3NE1334-2
A
500
2
) is based on a duty cycle of 110% for 60 s or 150% for 10 s with a duty cycle duration of 300 s
L
) is based on a duty cycle of 150% for 60 s or 160% for 10 s with a duty cycle duration of 300 s
H
7LE35-0AA0
250
400
380 V to 480 V 3 AC ± 10% (-15% < 1 min)
447
490
477
438
160
11.7
1.19
72/74
2 x 185
4 x 240
4 x (500)
M12 (2 holes)
2 x 185
2 x 240
2 x (500)
M12 (2 holes)
M12 (2 holes)
980
GI
GX
GX
1800 x 2,000 x 600
3NA3372
630
3
3NE1436-2
630
3
Operating Instructions, 07/07, A5E00288214A
7LE36-1AA0
315
500
549
605
590
460
100
15.9
1.96
77/79
2 x 240
4 x 240
4 x (500)
M12 (2 holes)
2 x 240
4 x 240
4 x (500)
M12 (2 holes)
M12 (2 holes)
1716
HI
HX
HX
2200 x 2,000 x 600
3NA3475
800
4
3NE1438-2
800
3