Siemens SINAMICS S150 Operating Instructions Manual page 298

Converter cabinet units 75 kw to 1200 kw
Hide thumbs Also See for SINAMICS S150:
Table of Contents

Advertisement

Output terminals
8.2 Analog outputs
Signals for the analog outputs: object A_INF
Table 8-3
List of signals for the analog outputs - object A_INF
Signal
Output current
DC link voltage
Modulation depth
Torque-generating current setpoint
Torque-generating actual current
Output power
Scalings for object A_INF
Table 8-4
Scalings for object A_INF
Variable
Reference frequency
Reference voltage
Reference current
Reference power
Reference modulation depth 100 % = Maximum output voltage without
Reference temperature
Example: changing analog output 0 from current to voltage output –10 V ... +10 V
298
Scaling parameter
100 % = p2000
100 % = p2001
100 % = p2002
100 % = r2004
overload
100% = 100°C
Parameter
Unit
r0068
Aeff
r0070
V
r0074
%
r0077
A
r0078
A
r0082
kW
p2000 = p0211
p2001 = r0206/r0207
p2002 = r0207
r2004 = r0206
Voltage output present at terminal 1, ground is at terminal 2
Set analog output type 0 to -10 ... +10 V.
Scaling (100 %=...)
See table below
p2002
p2001
Reference modulation depth
p2002
p2002
r2004
Default for quick commissioning
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A