Resetting AOP settings
When you choose this menu option, the AOP factory settings for the following are restored:
● Language
● Display (brightness, contrast)
● Operation screen
● Control settings
6.7.5.4

AOP30 diagnosis

Software/database version
You can use this menu to display the firmware and database versions.
The database version must be compatible with the drive software status (you can check this
in parameter r0018).
Battery status
In this menu, you can display the battery voltage numerically (in Volts) or as a bar display.
The battery ensures that the data in the database and the current time are retained.
When the battery voltage is represented as a percentage, a battery voltage of ≤ 2 V is equal
to 0%, and a voltage of ≥ 3 V to 100%.
The data is secure up to a battery voltage of 2 V.
● If the battery voltage is ≤ 2.45 V, the message "Replace battery" is displayed in the status
● If the battery voltage is ≤ 2.30 V, the system displays the following message: "Warning:
● If the battery voltage is ≤ 2 V, the system displays the following message: "Warning:
● If the time and/or database are not available after the system has been switched off for a
For instructions on how to change the battery, see "Maintenance and servicing".
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A
NOTICE
When you reset parameters, all settings that are different to the factory settings are
reset immediately. This may cause the cabinet unit to switch to a different, unwanted
operational status.
For this reason, you should always take great care when resetting parameters.
bar.
weak battery".
battery is empty".
prolonged period due to the voltage being too low, the loss is established by means of a
CRC check when the system is switched on again. This triggers a message instructing
the user to replace the battery and then load the database and/or set the time.
6.7 Control via the operator panel
Operation
229