Functions, monitoring, and protective functions
9.3 Drive functions
Note
The example described only applies to a SINAMICS S150 without option G61. With
option G61, steps 5 and 6 also have to be carried out for DO5 (2nd TM31).
Maximum output frequencies achieved by increasing the pulse frequency
By multiplying the basis pulse frequency (with integers), the following output frequencies can
be achieved (taking into account the derating factors):
Table 9-5
The maximum output frequency is limited to 300 Hz due to the closed-loop control.
1)
9.3.8.2

Parameters

• p0009
• p0112
• p0113
• p0115
• p1800
• p4099
330
Maximum output frequency achieved by increasing the pulse frequency
Pulse frequency
[kHz]
1,25
2
2,5
4
5
Device commissioning parameter filter
Sampling times pre-setting p0115
Selects the minimum pulse frequency
Sampling times
Pulse frequency
TM31 inputs/outputs, sampling time
Maximum output frequency
[Hz]
100
160
200
300
1)
300
1)
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A