Siemens SINAMICS S150 Operating Instructions Manual page 215

Converter cabinet units 75 kw to 1200 kw
Hide thumbs Also See for SINAMICS S150:
Table of Contents

Advertisement

NAMUR signaling bit bar
Table 6-17
NAMUR signaling bit bar
Bit
00
Fault, drive converter data electronics / SW error
01
Line supply fault
02
DC link overvoltage
03
Fault, drive converter power electronics
04
Overtemperature, drive converter
05
Ground fault
06
Motor overload
07
Bus error
08
External safety trip
09
Fault, motor encoder
10
Error, internal communications
11
Fault, infeed
15
Other faults/errors
Actual speed value (N_Act_A, N_Act_SMOOTH)
● Actual speed value with 16-bit resolution incl. sign bit.
● Bit 15 determines the actual value sign:
● The actual speed value is normalized via parameter p2000.
Actual speed (N_act_B)
● Actual speed value with 32-bit resolution incl. sign bit.
● Bit 31 determines the actual value sign:
● The actual speed value is normalized via parameter p2000.
Actual current value (Ia_Act, Ia_Act_SMOOTH)
● Actual current value with 16-bit resolution
● The actual current value is normalized via parameter p2002.
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A
Meaning
– Bit = 0 -> positive actual value
– Bit = 1 -> negative actual value
N_act_A = 4000 hex or 16384 dec = speed in p2000
– Bit = 0 -> positive actual value
– Bit = 1 -> negative actual value
N_act_B = 4000 0000 hex or 1073741824 dec = speed in p2000
Ia_act = 4000 hex or 16384 dec = current in p2002
6.6 PROFIBUS
0 signal
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
Operation
1 signal
215