Creating an S150 in SIMATIC Manager

Once you have called up the hardware manager, you have to choose the Profibus line to
which the S150 is to be connected.
In the catalog, double-click the S150 below the "Profibus-DP/Sinamics" folder. A window is
displayed in which you can set the S150 bus address. It must be the same as the address on
the converter (switch on CU320 or p0918).
To confirm your entries, choose OK. The "Configuration" tab is then displayed in the
"DP_Slave_Properties" window.
Figure 6-24
SIMATIC screen in HWConfig: DP slave properties S150
The number 1 is entered in the first field under "Object". Standard telegram 1 is defaulted in
the field under "Telegram selection".
To display a selection field in which you can select different telegram types, click the
standard telegram.
To display or change details (e.g. addresses for peripheral equipment) for the selected
telegram, choose the "Details" tab. If you want to use user-definable telegrams (p0922=999)
instead of standard telegrams, you can also change the number of PZDs here. The number
of PZDs in the send and receive direction does not have to be the same.
Once you have saved your configuration, you have to make a number of settings for the
converter. A distinction is made here between using the AOP and the STARTER
commissioning tool.
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A