Commissioning
5.5 First commissioning
5.5.2
Basic commissioning
Entering the motor data
During initial commissioning, you have to enter motor data using the operator panel. Use the
data shown on the motor type plate.
Figure 5-38
Table 5-1
Motor data
System of units for line frequency and entering
motor data
Motor:
Rated voltage
Rated current
Rated output
Rated power factor Cos (at p0100 = 0 only)
Rated efficiency (at p0100 = 1 only)
Rated frequency
Rated speed
160
Example of a motor type plate
Parameter no.
p0100
p0304
p0305
p0307
p0308
p0309
p0310
p0311
Values
Unit
0
IEC [50 Hz / kW]
1
NEMA [60 Hz / hp]
[V]
[A]
[kW] / [hp]
[%]
[Hz]
[min-1] / [rpm]
Operating Instructions, 07/07, A5E00288214A
Drive converter cabinet units