Siemens SINAMICS S150 Operating Instructions Manual page 196

Converter cabinet units 75 kw to 1200 kw
Hide thumbs Also See for SINAMICS S150:
Table of Contents

Advertisement

Operation
6.5 Setpoint sources
• p4059
• p4060
• p4063
Note
In the factory setting and after basic commissioning, an input current of 20 mA is equal to the
main setpoint 100 % reference speed (p2000), which has been set to the maximum speed
(p1082).
Example: Changing Analog Input 0 from Current to Voltage Input –10 to +10 V
Table 6-5
Note
The new analog input must then be stored on the CompactFlash card so that it is protected
in the event of a power failure.
F3505 – Fault: "Analog input, wire breakage"
The fault is triggered when analog input type (p4056) is set to 3 (4 ... 20 mA with open-circuit
monitoring) and the input current of 2 mA has been undershot.
The fault value can be used to determine the analog input in question.
Table 6-6
196
Analog inputs, characteristic value x2
Analog inputs, characteristic value y2
Analog inputs offset
Example: setting analog input 0
Current / voltage switchover
Set current/voltage selector to "Voltage" ("V").
Set analog input type 0 to -10 V... +10 V.
Fault screen
Component number
4: module -A60
5: module -A61 (optional)
0: Analog input 0: -X521:1/2
1: Analog input 1: -X521:3/4
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A