Defining the technological application / motor identification
Figure 5-29
35: Select the required data:
● Technological application:
● Motor identification:
36. Click Continue >.
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A
Defining the technological application / motor identification
– "Pumps and fans": edge modulation is enabled
– "Standard drive (VECTOR)": edge modulation is not enabled (default)
"Motor data identification with motor running" is normally the appropriate default setting
for SINAMICS S150, especially if an encoder is used for speed control.
5.3 Procedure for commissioning via STARTER
Commissioning