Siemens SINAMICS S150 Operating Instructions Manual page 43

Converter cabinet units 75 kw to 1200 kw
Hide thumbs Also See for SINAMICS S150:
Table of Contents

Advertisement

Item
Activity
9
With an external auxiliary supply, the cable for the 230 V AC supply must be connected
to terminal -X40 (see "Electrical installation / External supply of the auxiliary supply from
a secure line").
10
Option L10
dV/dt filter with
Voltage Peak
Limiter
11
Option L15
Sinusoidal filter
12
Option L19
Connection for
external
auxiliary
equipment
13
Option L50
Cabinet
illumination with
socket
14
Option L55
Anti-
condensation
heating for
cabinet
Signal connections
15
Cabinet unit operation by higher-level controller / control room. The control cables must
be connected in accordance with the interface assignment and the shield applied.
Taking into account electrical interference and the distance from power cables, the
digital and analog signals must be routed with separate cables.
When the analog inputs on the customer terminal block are used as current or voltage
inputs, selectors S5.0 and S5.1 must be set accordingly (see "Electrical installation /
Customer terminal block (-A60)").
16
Option K46
SMC10 Sensor
Module
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A
During commissioning, the filter must be selected via STARTER or
AOP30. You are advised to check the selection by ensuring that
p0230 is set to 2.
The required parameters are set automatically (see "Electrical
installation / dV/dt filter with Voltage Peak Limiter (option L10)").
During commissioning, the filter must be selected via STARTER or
AOP30. You are advised to check the selection by ensuring that
p0230 is set to 3.
The required parameters are set automatically (see "Electrical
installation / Sine-wave filter (option L15)").
To supply auxiliary equipment (e.g. separately-driven fan for motor),
the drive must be properly connected to terminals -X155:1 (L1) to
-X155:3 (L3). The supply voltage of the auxiliary equipment must
match the input voltage of the cabinet unit. The load current must not
exceed 10 A and must be set in accordance with the connected
consumer (see "Electrical installation / Connection for external
auxiliary equipment (option L19)").
The 230 V auxiliary supply for the cabinet illumination with an
integrated service socket must be connected to terminal -X390 and
protected with a fuse (max. 10 A) on the line side ("Electrical
installation / Cabinet illumination with socket (option L50)").
The 230 V auxiliary supply for the anti-condensation heating for the
cabinet (230 V / 50 Hz, 100 W / or 230 V / 50 Hz 2 x 100 W for
cabinets with a width of 800 to 1200 mm) must be connected to
terminals -X240: 1 to 3 and protected with fuses (max. 16 A) (see
"Electrical installation / Anti-condensation heating for cabinet (option
L55)").
The SMC10 Sensor Module is used for determining the actual motor
speed and the rotor position angle.
The following encoders are supported by the SMC10 Sensor Module:
Resolver, 2 pole
Resolver, multi-pole.
(See "Electrical installation / SMC10 Sensor Module for detecting the
actual motor speed and the rotor position angle (option K46)".)
Electrical installation
4.2 Checklist for electrical installation
Fulfilled/Complete
Set value:
_________________
43