Parameterization
Once the bypass with synchronizer with degree of overlapping (p1260 = 1) function has
been activated, the following parameters must be set:
Table 9-6
Parameter settings for bypass function with synchronizer with degree of overlapping
Parameters
p1266 =
Control signal setting when p1267.0 = 1
p1267.0 = 1
Bypass function is initiated by the control signal
p1267.1 = 0
p1269[0] =
Signal source for contactor K1 feedback
p1269[1] =
Signal source for contactor K2 feedback
p3800 = 1
The internal voltages are used for synchronization.
p3802 = r1261.2
Synchronizer activation is triggered by the bypass function.
Transfer process
Figure 9-10
Signal diagram, bypass with synchronization with overlap
Transfer of motor to line supply
(contactors K1 and K2 are activated by the converter):
● The initial state is as follows: Contactor K1 is closed, contactor K2 is open and the motor
● The control bit "bypass command" (p1266) is set (e.g., by the higher-level automation).
● The bypass function sets the control word bit "synchronizing" (r1261.2).
● Since the bit is set while the converter is running, the "Transfer motor to line supply"
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A
is fed from the converter.
synchronization process is started.
Functions, monitoring, and protective functions
Description
9.4 Extended functions
343