Mechanical installation
3.3 Installation
(option M54) can be installed in front of the hoods (IP54) and the ventilation grilles on the
cabinet doors.
The ambient conditions for the units in the operating rooms must not exceed the values of
code F in accordance with EN 60146. At temperatures > 40°C (104°F) and altitudes > 2000
m, the devices must be derated.
The basic version of the cabinet units complies with the IP20 degree of protection in
accordance with EN 60529.
The chassis units are installed in accordance with the dimension drawings supplied. The
clearance between the top of the cabinet unit and the ceiling is also specified on the
dimension drawings.
The cooling air for the power unit is drawn in from the front through the ventilation grilles in
the lower part of the cabinet doors. The warmed air is expelled through the perforated top
cover or the ventilation grilles in the top cover (with option M13/M23/M43/M54/M78). Cooling
air can also be supplied from below through raised floors or air ducts, for example. To allow
this, you have to create openings in the 3-section bottom plate.
According to EN 61800-3, the cabinet units are not suitable for use in low-voltage public
networks that supply residential buildings. High-frequency interference may occur if they are
used in this type of network.
Unpacking the cabinets
Check the delivery against the delivery note to ensure that all the items have been delivered.
Check that the cabinet is intact.
The packaging material must be discarded in accordance with the applicable country-specific
guidelines and rules.
Required tools
To install the connections, you will require:
● Spanner or socket spanner (w/f 10)
● Spanner or socket spanner (w/f 13)
● Spanner or socket spanner (w/f 16/17)
● Spanner or socket spanner (w/f 18/19)
● Hexagon-socket spanner (size 8)
● Torque wrench up to 50 Nm
● Screwdriver, size 2
● Screwdriver Torx T20
● Screwdriver Torx T30