Siemens SINAMICS S150 Operating Instructions Manual page 170

Converter cabinet units 75 kw to 1200 kw
Hide thumbs Also See for SINAMICS S150:
Table of Contents

Advertisement

Commissioning
5.8 Parameter reset to factory settings
Parameter reset via STARTER
With STARTER, the parameters are reset in online mode. The required steps are described
below:
Step
Choose
Project > Connect to target system
Click the drive unit whose parameters you want to reset to the factory settings
and click Restore factory settings icon in the toolbar.
To confirm, click OK.
Choose
Target system > Copy from RAM to ROM
Note
The Copy from RAM to ROM icon is only active when the drive unit is selected in the project
navigator.
When the parameters have been reset to the factory settings, initial commissioning needs to
be carried out.
170
Selection in toolbar
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A