Siemens SINAMICS S150 Operating Instructions Manual page 134

Converter cabinet units 75 kw to 1200 kw
Hide thumbs Also See for SINAMICS S150:
Table of Contents

Advertisement

Commissioning
5.3 Procedure for commissioning via STARTER
Configuring the drive unit properties
Figure 5-17
13. Under Standard, choose the appropriate standard for your motor,
whereby the following is defined:
● IEC motor (50 Hz, SI unit): line frequency 50 Hz, motor data in kW
● NEMA motor (60 Hz, US unit): line frequency 60 Hz, motor data in hp
14. Under Supply voltage the DC link voltage of the cabinet unit is specified (this should not
be changed).
15. Under Power unit application choose the appropriate application for your drive unit:
● Load duty cycle with high overload condition for vector drives (factory setting)
● Load duty cycle with slight overload condition for vector drives
16. Click Continue >.
134
Configuring the drive unit properties
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A