Siemens SINAMICS S150 Operating Instructions Manual page 433

Converter cabinet units 75 kw to 1200 kw
Hide thumbs Also See for SINAMICS S150:
Table of Contents

Advertisement

Preparatory steps
● Disconnect the cabinet unit from the power supply.
● Allow unimpeded access to the power block.
● Remove the protective cover.
Removal
The steps for the removal procedure are numbered in accordance with the diagram.
1. Unscrew the connection to the outgoing motor section (3 screws).
2. Unscrew the connection to the DC link (4 screws).
3. Remove the retaining screws at the top (2 screws).
4. Remove the retaining screws at the bottom (2 screws).
5. Remove the DRIVE-CLiQ cables and connections to the CU320 (5 plugs).
6. Remove the CU320 mounts (1 screw and 2 nuts). If necessary, remove the PROFIBUS
7. Disconnect the plugs for the fiber optic cables and signal cables (5 plugs).
8. Disconnect the plug for the thermocouple.
9. Unscrew the two retaining screws for the fan and attach the tool for de-installing the
You can now remove the power block.
CAUTION
When removing the power block, ensure that you do not damage any signal cables.
Installation
For re-installation, carry out the above steps in reverse order.
CAUTION
The tightening torques specified in the table "Tightening torques for connecting current-
carrying parts" must be observed.
Carefully re-establish the plug connections and ensure that they are secure.
The screwed connections for the protective covers must only be tightened by hand.
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A
plug and connection to the operator panel (-X140 on the CU320) and remove the CU320.
power block at this position.
Maintenance and servicing
11.4 Replacing components
433

Advertisement

Table of Contents
loading

Table of Contents