Table 7-1
p1300 V/f characteristics
Parameter
Meaning
value
0
Linear characteristic
1
Linear characteristic
with flux current
control (FCC)
2
Parabolic
characteristic
3
Programmable
characteristic
5
Precise frequency
drives
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A
Standard with variable voltage boost
Characteristic that compensates for voltage
losses in the stator resistance for static /
dynamic loads (flux current control FCC).
This is particularly useful for small motors,
since they have a relatively high stator
resistance.
Characteristic that takes into account the
motor torque curve (e.g. fan/pump).
Quadratic characteristic (f² characteristic)
Energy saving because the low voltage
also results in small currents and losses.
Characteristic that takes into account the
motor/machine torque characteristic.
Characteristic (see parameter value 0) that takes into account the technological
particularity of an application (e.g. textile applications):
Whereby current limitation (Imax controller) only affects the output voltage and not
the output frequency.
By disabling slip compensation.
Setpoint channel and closed-loop control
Application / property
V
V
n
0
V
V
n
0
V
V
max
r0071
p1327
p1325
p1323
p1321
r1315
0
f1
p1320
7.3 V/f control
f
f
n
f
f
n
f
f 4
f max
f2
f3
p1322
p1324
p1326
p1082