Procedure
1. Select the inserted drive in the hardware catalog.
2. Drag the Parameter Access Point entry to slot 1 in the station window of the drive.
3. For the first drive object (DO), drag the appropriate telegram for cyclic data transfer to the
4. Repeat steps 2 and 3 for each drive object for which cyclic data is to be exchanged.
5. The project must be saved and compiled once all of the drive objects have been inserted.
6. Assigning the device name.
7. Configuration in HW Config is now complete.
RT communications with GSDML v2.0
Requirement
For example, a 300 CPU version 2.5 or higher with a PROFINET IO with RT sub-network
has been configured and a drive inserted via the GSD file SINAMICS S120 CBE20.
Now, drives and drive objects (DOs) are to be parameterized. For this version of the GSDML
file, the telegrams can be inserted one after the other.
Note
The sequence of the telegram structure must match the sequence of the drive objects in the
configuration screen of the drive in STARTER.
Procedure
1. Select the inserted drive in the hardware catalog.
2. For the first drive object (DO), drag the appropriate telegram for cyclic data transfer to the
3. Repeat step 2 for each drive object for which cyclic data is to be exchanged.
4. The project must be saved and compiled once all of the drive objects have been inserted.
5. Double-click the drive unit. A dialog containing the properties of the IO device is
6. Configuration in HW Config is now complete.
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A
next slot of the station window.
Check the "IP address assignment via controller" box for volatile assignment of the IP
address for the configured IO controller and IO device during power-up. The configured
device name must match the device name of the IO device.
next slot of the station window. A parameter access point is added automatically.
displayed.
Check the "IP address assignment via controller" box for volatile assignment of the IP
address for the configured IO controller and IO device during power-up. The configured
device name must match the device name of the IO device.
Operation
6.8 PROFINET IO
253