Siemens SINAMICS S150 Operating Instructions Manual page 414

Converter cabinet units 75 kw to 1200 kw
Hide thumbs Also See for SINAMICS S150:
Table of Contents

Advertisement

Diagnosis / faults and alarms
10.2 Diagnosis
SMC20 – encoder evaluation (-A82)
Table 10-7
Description of the LEDs on the SMC20
LEDs
Color
RDY
---
Green
Orange
Red
Green/red
Green/orange
or
red/orange
SMC30 – encoder evaluation (-A81)
Table 10-8
Description of the LEDs on the SMC30
LED
Color
RDY
---
Green
Orange
Red
Green / red
Green Orange
or
Red Orange
OUT>5 V
---
Orange
414
Status
OFF
The electronics power supply is missing or lies outside the
permissible tolerance range.
Continuous
The component is ready for operation and cyclic DRIVE-CLiQ
communication is taking place.
Continuous
DRIVE-CLiQ communication is being established.
Continuous
At least one fault is pending on this component.
Note:
LED is driven irrespective of the corresponding messages being
reconfigured.
0.5 Hz flashing light Firmware is being downloaded.
2 Hz flashing light
Firmware download is complete. Wait for POWER ON.
2 Hz flashing light
Detection of the components via LED is activated (p0144).
Note:
Both options depend on the LED status when module recognition is
activated via p0144 = 1.
State
OFF
The electronics power supply is missing or lies outside permissible
tolerance range.
Steady light
The component is ready for operation and cyclic DRIVE-CLiQ
communication is taking place.
Steady light
DRIVE-CLiQ communication is being established.
Steady light
At least one fault is pending on this component.
Note:
LED is driven irrespective of the corresponding messages being
reconfigured.
0.5 Hz flashing light
Firmware is being downloaded.
2 Hz flashing light
Firmware download is complete. Waiting for POWER ON.
2 Hz flashing light
Detection of the components via LED is activated (p0144).
Note: Both options depend on the LED status when module
recognition is activated via p0144 = 1.
OFF
Electronic power supply missing or outside permissible tolerance
range.
Measuring system supply ≤ 5 V (only when ready for operation).
Steady light
Electronic power supply for measuring system present.
Measuring system supply > 5 V.
Notice: You must ensure that the connected encoder can be
operated with a 24 V supply.
Operating an encoder designed for a 5 V supply with a 24 V supply
can damage the encoder electronics beyond repair.
Description
Description
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A