Connection For External Auxiliary Equipment (Option L19) - Siemens SINAMICS S150 Operating Instructions Manual

Converter cabinet units 75 kw to 1200 kw
Hide thumbs Also See for SINAMICS S150:
Table of Contents

Advertisement

4.9.3

Connection for external auxiliary equipment (Option L19)

Description
This option includes an outgoing circuit fused at max. 10 A for external auxiliary equipment
(e.g. separately-driven fan for motor). The voltage is tapped at the converter input upstream
of the main contactor/circuit-breaker and, therefore, has the same level as the supply
voltage. The outgoing circuit can be switched within the converter or externally.
Connection
Table 4-21
Terminal
Max. connectable cross-section: 4mm² (AWG 10)
Note
The connection for external auxiliary equipment must be set in accordance with the
connected consumer (-Q155).
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A
Terminal block X155 - Connection for external auxiliary equipment
Designation
1
L1
2
L2
3
L3
11
Contactor control
12
13
Checkback from
circuit breaker
14
15
Checkback from
contactor
16
PI
PI
Electrical installation
4.9 Other connections
Technical activities
380 - 480 V 3 AC
660 - 690 V 3 AC
500 - 690 V 3 AC
230 V AC
230 V AC / 0.5 A
24 V DC / 2 A
240 V AC / 6 A
PI
71

Advertisement

Table of Contents
loading

Table of Contents