7.4.4

Closed-loop torque control

Description
For sensorless closed-loop speed control (p1300 = 20) or closed-loop speed control with
encoder VC (p1300 = 21), it is possible to change over to closed-loop torque control using
BICO parameter p1501. It is not possible to change over between closed-loop speed and
torque control if closed-loop torque control is directly selected with p1300 = 22 or 23. The
torque setpoint and/or supplementary setpoint can be entered using BICO parameter p1503
(CI: torque setpoint) or p1511 (CI: supplementary torque setpoint). The supplementary
torque acts both for closed-loop torque as well as for the closed-loop speed control. As a
result of this characteristic, a pre-control torque can be implemented for the closed-loop
speed control using the supplementary torque setpoint.
Note
For safety reasons, assignments to fixed torque setpoints are currently not possible.
If energy is regenerated and cannot be injected back into the line supply, then a Braking
Module with connected braking resistor must be used.
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A
Speed setpoint, droop
Total speed setpoint
Speed controller I torque output
Droop input source
Droop feedback scaling
Droop feedback speed reduction
Droop feedback enable
Torque setpoint before supplementary torque
Setpoint channel and closed-loop control
7.4 Vector speed/torque control with/without encoder