Operation
6.6 PROFIBUS
Setting the PROFIBUS ID number
The PROFIBUS Ident Number (PNO-ID) can be set using p2042.
SINAMICS can be operated on PROFIBUS with various identities, This allows a PROFIBUS
GSD that is independent of the device to be used (e.g. PROFIdrive VIK-NAMUR with Ident
Number 3AA0 hex).
● 0: SINAMICS S/G
● 1: VIK-NAMUR
A new setting only becomes effective after POWER ON, reset or download.
Note
The advantages of Totally Integrated Automation (TIA) can only be utilized when selecting
"0".
6.6.3

Monitoring: Telegram failure

Description
Following a telegram failure and after a monitoring time has elapsed (t_An), bit r2043.0 is set
to "1" and alarm A01920 is output. Binector output r2043.0 can be used for an emergency
stop, for example.
Once a delay time (p2044) has elapsed, fault F01910 is output and fault reaction OFF3
(quick stop) is triggered. If no OFF response is to be triggered, the fault response can be
reparameterized accordingly.
Fault F01910 can be acknowledged immediately. The drive can then be operated even
without PROFIBUS.
Figure 6-23
204
Monitoring: Telegram failure
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A