PTX10000 Rack Requirements
The PTX10000 router chassis are designed to be installed in four-post racks.
Rack requirements consist of:
Rack type
Rack mount kit hole spacing
Rack size and strength
Rack connection to the building structure
Table 51 on page 155
provides the rack requirements and specifications for the PTX10008 and the PTX10016
routers.
Table 51: Rack Requirements for the PTX10000
Rack Requirement
Rack type: four-post
Rack mount kit hole spacing
Guidelines
Use a TELECT 2000 lb four-post rack that provides bracket holes or hole
patterns spaced at 1 U (1.75 in. or 4.45 cm) increments and that meets
the size and strength requirements to support the weight.
A U is the standard rack unit defined in Cabinets, Racks, Panels, and
Associated Equipment (document number EIA-310–D) published by the
Electronics Industry Association.
You can stack one PTX10016 router or one PTX10008 router at the
bottom of the four-post rack if:
The rack is 42 U or greater.
The rack meets the strength requirements to support the weight.
The facility can provide adequate power and cooling.
The holes in the rack mount kit are spaced at 1 U (1.75 in. or 4.45 cm),
so that the router can be mounted in any rack that provides holes spaced
at that distance.