Alarm reporting principles

Event conditions

See "Reporting codes used in Advisor Advanced" on page 223 for a list of events
that can be reported to central stations.
When a new event occurs, the system performs a few checks below before it is
reported to central stations.
Is it mapped to any central station?
Every event in Advisor Advanced system has defined a particular set of central
stations that it can be reported to. It is done via menu "9.2.1 CS mapping" on
page 172.
For example, central station 1 is the Fire Brigade Station. All fire events then can
be mapped to CS 1. CS 3 is a security company, which monitors burglar alarms.
Burglar events as well as tamper alarms are mapped to it.
If the event is not mapped, is not reported anywhere.
Is this event already waiting for reporting?
If exactly the same event (from the same area and source) is already waiting for
reporting, such event will be reported only once.
Are there restored events?
There are two possible situations when two consecutive events are ignored
during reporting:
The new event is a restoring event for the other one, which is already waiting
for reporting.
The new event is an event, which restoring event is already waiting for
reporting.
If the first complementary event is configured as a delayed one in "9.2.3 Delayed
events" menu on page 172, both events are excluded from reporting.
For example, burglar alarm (BA) from area 1 is a delayed event, and the delay
time is 30 seconds. The event is mapped to CS 1, as well as burglar restore
event (BR). When there is an alarm in area 1, the event is waiting for reporting.
When the user disarms the area and acknowledges the alarm, the burglar restore
event occurs. If the user does it before 30-second delay times out, no information
is sent to the central station 1.
Note:
The events do not exclude each other if they are mapped to different
central stations.
Is this event a part of the combined OP/CL reporting?
If "9.1.n.9 OP/CL report" on page 167 is set to combined, only the initial area
disarming (opening) and the final area arming (closing) in the group of areas with
206