1.2.6.n.2 Period / Time
1 Period
>4<
If "1.2.6.n.1 Test call mode" on page 54 is set to Period, the menu defines the
interval between automatic test calls. The allowed range is 0 (never repeat) to
999 hours.
Note:
The first test call occurs after a panel restart or a configuration change.
If the option "1.2.6.n.3 Extend" below is set to Yes, the real time of the test call
can vary depending on other events reported to the central station.
If "1.2.6.n.1 Test call mode" on page 54 is set to Time, the menu defines the time
when the test call occurs. The test call time is set in 24 h format, as HH:MM.
1.2.6.n.3 Extend
3 Extend
>No<
The Extend option defines whether the test call interval is counted from the
previous test call or from the last successful event report.
If this option is set to Yes, after an event transmitted to the central station the test
call delay is extended and the next test call is postponed.
If this option is set to No, the next test call occurs in a test call period after the
previous test call, regardless of other reported events.
The option is only applicable if "1.2.6.n.1 Test call mode" on page 54 is set
Note:
to Period.
1.2.6.n.4 Freq TC if FTC
4 Freq TC if FTC
>No<
If this option is set to Yes, during the communication fault (FTC) the panel tries to
establish a communication by initiating a test call every hour. Otherwise, the test
call is attempted as usual depending on the "1.2.6.n.2 Period / Time" option
described above.
1.2.6.n.5 Man. test call
Calling CS 1...
Ready
The Manual test call option lets you test the central station reporting. Select the
central station. The panel now tries to establish a connection with the selected
central station.
The call progress status is shown on the display.
Advisor Advanced ATSx000A(-IP) Installation and Programming Manual