When all zones are tested successfully, the following message is displayed.
Walk test OK
Press ENTER
The test is cancelled if the Clear key is pressed. There is also a maximum time
limit on the test, set in "8.1.3.3 Walk test time" (see page 140). The test fails if
this timer expires. If engineer reset fails and inhibit reporting has not been
enabled when accessing the programming mode then a message is sent to the
central station to indicate that the test failed (see "Reporting codes used in
Advisor Advanced" on page 223).
1.2.5.2 Walk test opts
1>Use int siren
Yes
The Options menu allows setting up the following walk test options.
1.2.5.2.1 Use internal siren
1 Use int siren
>Yes<
If the Use internal siren option is set to Yes, each tested zone activation is
signalled by the internal siren.
1.2.5.2.2 Use buzzers
2 Use buzzers?
>No<
If set to Yes, each tested zone activation is signalled by keypad buzzers.
1.2.5.2.3 Log untested
3 Log untested
>Yes<
If the Log untested option is set to Yes, untested zones are recorded in the
system log.
1.2.5.2.4 Zone tamper
4 Zone tamper
>Yes<
If the Zone tamper option is set to Yes, the zone tamper is included into the walk
test.
1.2.5.2.5 Rkp/Exp tamper
5 Rkp/Exp tamper
>No<
If the Keypad/expander tamper option is set to Yes, the tamper alarms from
keypads and expanders assigned to this area also have to be tested.
52