Example: Panel tampers.
8. Exit terminator
This zone type is used to terminate an exit time. If the zone switches from active
to normal, the exit time is terminated and the area(s) are completely set as soon
as the final set delay has expired (see also "8.1.3.5 Final set delay" on page
140").
9. Keyswitch
When the zone switches, the area is set / unset / part set depending on the zone
options selected.
Example: Key switch next to Front door.
See options "4.1.n.6.15 Key latch" on page 99, "4.1.n.6.16 Key set" on page 100,
"4.1.n.6.17 Key unset" on page 100.
10. Medical
Generates a medical alarm regardless of the status of the area.
11. Technical
Generates a technical alarm regardless of the status of the area.
Example: temperature sensor.
See options "4.1.n.6.18 Technical full set" on page 100, "4.1.n.6.19 Technical
unset" on page 100.
12. Transmission path fault
Monitors the external reporting device.
13. Fire door
If there is no fire alarm present, generate an intrusion alarm regardless of the
status of the area. Otherwise no intrusion alarm is generated.
Example: Fire doors or emergency doors.
See also "4. Fire" on page 233.
14. Aux mains fault
Monitors the auxiliary mains supply.
15. Aux batt fault
Monitors battery of the auxiliary power supply.
16. Key box
Monitors a box that holds a key to premises. It allows you to open for a short
period after setting an area (specified in key box timer, see "8.1.4.5 Key box
time" on page 142). It generates an alarm when opened outside of this period.
234