Storing Cables - Fujitsu M10 Installation Manual

Hide thumbs Also See for M10:
Table of Contents

Advertisement

Figure 5-13     Serial port location
2.
Confirm that the SPARC M10-4S and crossbar box power cords are
connected to the PDUs of the expansion rack.
The SPARC M10-4S and crossbar box power cords are shipped connected to the
PDUs of the expansion rack.
If the SPARC M10-4S has been mounted on site, connect the power cords to the
PDUs at this time.
3.
Confirm that the CB switches of the PDUs of the expansion rack are OFF.
5.5

Storing Cables

This section describes the procedure for storing the cables connected to the SPARC
M10-4/SPARC M10-4S in a rack.
The procedures for storing the cables in the rack are described separately for the rack
widths of 700 mm and 600 mm. Check your rack before performing this work.
Note - For an expansion rack, crossbar cables (optical) and XSCF cables are stored in the rack
at the time of shipping, so this work is not necessary.
5.5.1
Rack with a width of 700 mm (27.6 in.)
For a rack with a width of 700 mm (27.6 in.), keep the power cords together at the left
side and the other cables at the right side, as viewed from the rear of the rack.
1.
Hang the power cords from the left side as viewed from the rear of the rack.
Place the power cords over the cable support fixing bracket (A in
hang them there as is.
Fujitsu M10/SPARC M10 Systems Installation Guide ・ July 2015
172
A
Figure
5-14) to