Table 2-12     Electrical specifications (SPARC M10-4S)
Item
Input voltage
Number of power cords
Power cord length
Redundancy
Frequency
Rated current (*1)
Maximum power
consumption
Apparent power
Rush current (*2)
Leakage current (*2)
*1 The current that flows through each power cord in a redundant configuration is half the value listed in
2-12.
*2 The value is per power cord.
Table 2-13     Electrical specifications (Expansion rack: Single-phase power feed model) (*1)
Item
Input voltage
Number of power cords
Power cord length
Redundancy (*2)
Frequency
Rated current (*3)
Rated current (*4) (*5)
Maximum power consumption (*4)
Apparent power (*4)
Rush current (*3) (*4)
Fujitsu M10/SPARC M10 Systems Installation Guide ・ July 2015
56
Specification
CPU type: SPARC64 X
200 to 240 VAC
2 (1 for each PSU)
Maximum length of 3.0
m (9.8 ft.)
1+1 redundant
configuration
50 Hz/60 Hz, single
phase
Japan
14.8 A
Outside Japan
14.2 A
Japan
2,905 W
Outside Japan
2,779 W
Japan
2,964 VA
Outside Japan
2,836 VA
45 A peak or less
1.75 mA
Specification
1 expansion rack
200 to 240 VAC
8
4.0 m (13.1 ft.)
1+1 redundant configuration
50 Hz/60 Hz
Maximum of 40 A
6.9 A
1,354 W
1,382 VA
80 A peak or less
CPU type: SPARC64 X+
16.0 A
16.0 A
3,425 W
3,299 W
3,495 VA
3,366 VA
2 expansion racks
200 to 240 VAC
8
4.0 m (13.1 ft.)
1+1 redundant configuration
50 Hz/60 Hz
Maximum of 40 A
9.0 A
1,754 W
1,790 VA
80 A peak or less
Table