Table 2-13     Electrical specifications (Expansion rack: Single-phase power feed model) (*1) (continued)
Item
Input voltage
Leakage current (*3) (*4)
*1 The specifications apply to a single rack.
*2 For the M10-4S mounted in an expansion rack. If the mounted device is not the M10-4S, the configuration may be different depending
on the power connection configuration of the device.
*3 The value is the tolerance per power cord. The actual current value depends on the rating of the device mounted in the expansion rack.
*4 The value is for an expansion rack without the M10-4S and other devices mounted. (Only crossbar boxes are mounted.)
Only the two power cords use power.
If the M10-4S or other devices are mounted, the current values and the number of power cords that consume power are different.
*5 The current that flows through each power cord in a redundant configuration is half the value listed in
Table 2-14     Electrical specifications (Expansion rack: Three-phase delta power feed model) (*1)
Item
Input voltage
Number of power cords
Power cord length
Redundancy (*2)
Frequency
Rated current (*3)
Rated current (*4) (*5)
Maximum power consumption (*4)
Apparent power (*4)
Rush current (*3) (*4)
Leakage current (*3) (*4)
*1 The specifications apply to a single rack.
*2 For the M10-4S mounted in an expansion rack. If the mounted device is not the M10-4S, the configuration may be different depending
on the power connection configuration of the device.
*3 The value is the tolerance per power cord. The actual current value depends on the rating of the device mounted in the expansion rack.
*4 The value is for an expansion rack without the M10-4S and other devices mounted. (Only crossbar boxes are mounted.)
Only the two power cords use power.
If the M10-4S or other devices are mounted, the current values and the number of power cords that consume power are different.
*5 The current that flows through each power cord in a redundant configuration is half the value listed in
Table 2-15     Electrical specifications (Expansion rack: Three-phase star power feed model) (*1)
Item
Input voltage
Number of power cords
Power cord length
Specification
1 expansion rack
200 to 240 VAC
3.5 mA
Specification
1 expansion rack
200 to 240 VAC
6
4.0 m (13.1 ft.)
1+1 redundant configuration
50 Hz/60 Hz
Maximum of 35 A
4.0 A
1,354 W
1,382 VA
80 A peak or less
3.5 mA
Specification
1 expansion rack
380 to 415 VAC
6
4.0 m (13.1 ft.)
Chapter 2 Planning and Preparing for System Installation
2 expansion racks
200 to 240 VAC
3.5 mA
Table
2-13.
2 expansion racks
200 to 240 VAC
6
4.0 m (13.1 ft.)
1+1 redundant configuration
50 Hz/60 Hz
Maximum of 35 A
5.2 A
1,754 W
1,790 VA
80 A peak or less
3.5 mA
Table
2-14.
2 expansion racks
380 to 415 VAC
6
4.0 m (13.1 ft.)
57