Table 2-9     Cooling conditions (continued)
Configuration
Input voltage
200 to 240 VAC
SPARC M10-4
200 to 240 VAC
SPARC M10-4S
200 to 240 VAC
Configuration
200 to 240 VAC
including only
(*2)
expansion rack 1
200 to 240 VAC
(*1)
(*3)
380 to 415 VAC
(*4)
Configuration
200 to 240 VAC
including
(*2)
expansion rack 2
200 to 240 VAC
(*1)
(*2)
380 to 415 VAC
(*4)
PCI expansion
AC100 - 120 V
unit
200 to 240 VAC
*1 The SPARC M10-4S is not mounted.
*2 Value for the single-phase power feed model
*3 Value for the three-phase delta power feed model
*4 Value for the three-phase star power feed model
Fujitsu M10/SPARC M10 Systems Installation Guide ・ July 2015
42
CPU type
Region
Outside
Japan
SPARC64 X
Japan
Outside
Japan
SPARC64 X+ Japan
Outside
Japan
SPARC64 X
Japan
Outside
Japan
SPARC64 X+ Japan
Outside
Japan
SPARC64 X
Japan
Outside
Japan
SPARC64 X+ Japan
Outside
Japan
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Maximum heat dissipation
2,900 kJ/hr (2,750 BTU/hr)
2,820 kJ/hr (2,670 BTU/hr)
2,660 kJ/hr (2,520 BTU/hr)
2,970 kJ/hr (2,810 BTU/hr)
2,820 kJ/hr (2,670 BTU/hr)
10,410 kJ/hr (9,864 BTU/hr)
9,954 kJ/hr (9,434 BTU/hr)
11,550 kJ/hr (10,950 BTU/hr)
11,100 kJ/hr (10,520 BTU/hr)
10,460 kJ/hr (9,912 BTU/hr)
10,000 kJ/hr (9,482 BTU/hr)
12,330 KJ/hr (11,690 BTU/hr)
11,880 KJ/hr (11,260 BTU/hr)
4,876 kJ/hr (4,622 BTU/hr)
4,876 kJ/hr (4,622 BTU/hr)
4,876 kJ/hr (4,622 BTU/hr)
6,316 kJ/hr (5,988 BTU/hr)
6,316 kJ/hr (5,988 BTU/hr)
6,316 kJ/hr (5,988 BTU/hr)
1,005 kJ/hr (953 BTU/hr)
972 kJ/hr (921 BTU/hr)
Maximum
exhaust
airflow
17.1 m
3
/min
3
18.7 m
/min
17.1m
3
/min
3
18.7m
/min
3
29.8 m
/min
3
29.8 m
/min
3
4.5 m
/min

Advertisement

Table of Contents
loading

Table of Contents