Advertisement

power cord. Order the power cords that match the device. Always connect the
power cords to grounded power outlets.
When using an expansion rack, be sure to use the supplied power cords.
To confirm the type of power supplied by the building, contact the facility
administrator or a certified electrician.
For three-phase input
No power cord is supplied for three-phase input. Grounded power cords must be
connected from the distribution panel directly to the terminal boards of power
supply chassis as part of local electrical work.
When using an expansion rack, be sure to use the supplied power cords.
Although common grounding is possible with this device, grounding methods
vary depending on the building of the installation. When using common
grounding, ground devices such that the grounding resistance is equal to or less
than 10 ohms. Be sure to have the facility administrator or a certified electrician
confirm the grounding method for the building and perform the grounding work.
Do not connect to an IT power system.
2.10
Checking External Interface Port
Specifications
This section provides an overview of the specifications of the external interface ports
required in installation and operation of the SPARC M10 systems.
 
You can use the following external interface ports on the SPARC M10 systems.
XSCF unit administration port
Serial port
The eXtended System Control Facility (XSCF) has one RS-232C-compliant serial
port. You can monitor and control the system by connecting the system
management terminal to the serial port. Functions that require TCP/IP are not
available through the serial port.
XSCF-LAN port
In addition to the serial port, the XSCF has two 1000BASE-T LAN ports. You can
remotely monitor and control the system by configuring a system control network
using a LAN port. There are two types of interfaces available: a command-line
interface (XSCF shell) and a browser user interface (XSCF Web).
Do not make a connection with a network switch or hub until you complete the
network setting for the XSCF. If a connection is made before the completion of the
setting, devices connecting with others may become unable to communicate, or
unauthorized login by a malicious third party to the XSCF of this chassis may be
unable to be prevented.
Fujitsu M10/SPARC M10 Systems Installation Guide ・ July 2015