Attach the rail such that the spring-loaded side (B in
and the flange (C in
a. From the front of the rack, insert the rail protrusions into 2U top and 1U top
in the front supporting column of the rack.
b. Pull out the rail to as far as the depth of the rack.
c. Insert the rail protrusions into 2U top and 1U bottom in the rear supporting
column of the rack.
d. Secure the rail with one M6 screw to the front supporting column of the rack.
The fixing location is 2U bottom.
e. Attach the other rail in the same manner.
Figure 3-72     Attaching the Type-1 rail: Locations of protrusions
Mounting
area (2U)
FRONT
- For the Type-2 rail
The letter [R] on a side of a rail indicates that the side is the front right side, and
[L] indicates that the side is the front left side.
a. From the rear of the rack, insert the rail protrusion into 1U top in the front
supporting column of the rack.
b. Pull out the rail to as far as the depth of the rack.
c. Insert the rail protrusion into 2U top in the rear supporting column of the
rack.
d. Secure the rail with one M6 screw to the front supporting column of the rack.
The fixing location is 2U bottom.
e. Attach the other rail in the same manner.
Figure
3-70) faces the bottom.
2U top
1U top
1U bottom
REAR
Figure
3-70) faces the front
Mounting
area (2U)
Chapter 3 Installing the System
127