How To Connect And Configure A Run/Stop Switch; With Forward/Reverse Selection - Mitsubishi Electric D700-SC Easy Start Manual

Table of Contents

Advertisement

Easy Start Guide
Mitsubishi D700-SC Series Inverter

11. How to connect and configure a Run/Stop switch

with Forward/Reverse selection

The procedure described in section 7 enables
Run/Stop operation via the red and green
buttons on the Inverter keypad.
If this is unsuitable for the application, remote
switches can be used instead.
11.1 Parameters to change for remote Run/Stop
Parameter Description
Pr. 2
Minimum Speed
Pr. 178
STF terminal function selection
Pr. 179
STR terminal function selection
Pr. 250
Stop Selection
1
2
Switch, 2 Position
Normally Open
"Run / Stop"
This guide has been produced by The Inverter Drive Supermarket Ltd.
All content, including but not limited to graphics, text and procedures copyright
Drive Supermarket and must not be reproduced or altered without prior written permission.
How to set
Set to
5.00
to run the motor at 5Hz if no other speed reference has been defined.
Set to
60
for forward rotation selection. This is the factory default.
Set to
61
for reverse rotation selection. This is the factory default.
Default is 9999. Set to
1 2 3
1
3
R
Switch, 2 Position
Normally Open
"Forward / Reverse"
This section explains how to enable 2-wire
control with Run/Stop and Forward/Reverse
commands via separate selector switches.
The Inverter must be in "EXT" control mode to
operate from the I/O terminals. Press PU/EXT
to select.
8888
for Run with Forward/Reverse selection.
11.2 Connecting the Switch
A wiring diagram is shown in the illustration
opposite.
The PC terminal is a common connection for
terminals RL, RM, RH, STF and STR when the
jumpers are set in "Source" (the default). If the
jumpers have been changed to "Sink", use SD as
the common instead.
Two suitable 2 position NO (Normally Open)
switches should be installed: One between
terminals PC and STF (Run/Stop) and the other
b e t w e e n t e r m i n a l s P C a n d S T R
(Forward/Reverse).
Note that the Forward/Reverse switch only selects
the direction of rotation - it will not start or stop the
motor. The direction can be set either before the
motor is started or whilst it is running.
If the application only requires the motor to turn in
one direction, the Forward/Reverse switch can be
omitted.
The Inverter must be in external control mode to
operate in 3-wire control. Check that the "EXT"
indicator is illuminated to confirm. The PU/EXT key
can be used to change the mode if required.
©
The Inverter
Page 11